ANTERO RSVR, COLORADO

Period of Record General Climate Summary - Heating Degree Days

Station:(050263) ANTERO RESERVOIR
From Year=1961 To Year=2012
Heating Degree Days for Selected Base Temperature (F)
Base Jan. Feb. Mar. Apr. May Jun. Jul. Aug. Sep. Oct. Nov. Dec. Annual
65 1566 1355 1234 930 663 383 209 271 485 841 1189 1541 10666
60 1411 1214 1079 780 508 236 73 124 336 686 1039 1386 8869
57 1318 1129 986 690 415 155 25 57 248 593 949 1293 7858
55 1256 1072 924 630 354 110 10 29 192 531 889 1231 7228
50 1101 931 769 480 210 35 1 3 81 377 739 1076 5803
Heating Degree Day units are computed as the difference between the base temperature and the daily average temperature. (Base Temp. - Daily Ave. Temp.) One unit is accumulated for each degree Fahrenheit the average temperature is below the base temperature. Negative numbers are discarded. Example: If the days high temperature was 65 and the low temperature was 31, the base 50 heating degree day units is 50 - ((65 + 31) / 2) = 2. This is done for each day of the month and summed.
Table updated on Oct 31, 2012
Months with 5 or more missing days are not considered
Years with 1 or more missing months are not considered

Western Regional Climate Center, wrcc@dri.edu